The exceptionally easy-to-use and popular S8JX Series now includes models with harmonic current suppression. That means more variations for a wider range of selections.
The exceptionally easy-to-use and popular S8JX Series now includes models with harmonic current suppression. That means more variations for a wider range of selections.
General-purpose Power Supplies that are exceptionally easy to use and feature a short body.
Install even 300-W models with either screws or DIN Rail.
* Screw mounting must be used with 600-W models.
* For 300-W models, use steel DIN Rail.
Use the S8JX as a 15-W to 150-W DC/DC Power Supply.
* Not applicable to 150-W, 5-V models.
Thinner panels can be achieved without interfering with other components.
Comparison to Previous OMRON 50-W Front-mounting Models
* (24V/48V)
Harmonic current suppression enables a wider range of application.
* Applies to 300-W and 600-W models only.
You can compensate for voltage drops on the load lines.
Use an external signal to turn the output ON and OFF while the input voltage is applied.
Output a signal for Power Supply errors, such as fan failure or insufficient voltage.
(For 200-V Input)
Ensure reliable operation even for momentary drops in the input voltage.
Applications include semiconductor manufacturing equipment.
* S8JX-P 300-W model with fan.
Input specification | 100 to 240 V input | |||
---|---|---|---|---|
Power ratings *1 | 15 W | 35 W | ||
Efficiency | 68% min. | 73% min. | ||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9) | ||
Frequency *2 | 50/60 Hz (47 to 450 Hz) | |||
Current *3 |
100 V input | 0.4 A max. | 1 A max. | |
200 V input | 0.25 A max. | 0.6 A max. | ||
Harmonic current emissions | --- | |||
Leakage current *3 |
100 V input | 0.5 mA max. | ||
200 V input | 1 mA max. | |||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 20 A max. | ||
200 V input | 40 A max. | |||
Output *4 |
Voltage adjustment range *5 | - 10% to 15% (with V. ADJ) (48-V models: ± 10%) | ||
Ripple *3 | 2% (p-p) max. | |||
Input variation influence | 0.4% max. with AC input voltage | |||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | |||
Temperature variation influence | 0.05%/ °C max. (at rated input and output) | |||
Startup time | 500 ms max. (up to 90% of output voltage at rated input and output) | |||
Hold time *3 | 20 ms min. | |||
Addi- tional func- tions |
Overload protection *6 |
105% to 175% of rated load current, voltage drop, intermittent, automatic reset |
||
Overvoltage protection *7 | Yes | |||
Overheat protection | No | |||
Parallel operation | No (However, backup operation is possible; external diodes required.) | |||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||
Protective circuit operation indicator |
No | |||
Other | Ambient operating temperature |
Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
||
Storage temperature | - 25 to 65 °C (with no icing or condensation) | |||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength |
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) |
|||
Insulation resistance |
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
|||
Vibration resistance |
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
|||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||
Output indicator | Yes (Color: Green) | |||
EMI |
Conducted Emissions |
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9 | ||
Radiated Emissions | Conforms to EN 55011 Group 1 Class A *9 | |||
EMS |
Electrostatic Discharge |
Conforms to EN61000-4-2 | ||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | |||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | |||
Surge | Conforms to EN61000-4-5 | |||
Conducted Disturbance |
Conforms to EN61000-4-6 | |||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | |||
Approved standards *9 | UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) | |||
cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 |
||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
||||
SEMI | SEMI F47-0200 (200-VAC input) | |||
Weight *8 | 250 g max. |
Input specification | 100 to 240 V input | |||
---|---|---|---|---|
Power ratings *1 | 50 W | 100 W | ||
Efficiency | 5 V Models | 76% min. | 76% min. | |
12 V Models | 81% min. | 81% min. | ||
24 V Models | 83% min. | 83% min. | ||
48 V Models | 82% min. | 83% min. | ||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9) | ||
Frequency *2 | 50/60 Hz (47 to 450 Hz) | |||
Current *3 |
100 V input | 1.4 A max. | 2.5 A max. | |
200 V input | 0.8 A max. | 1.5 A max. | ||
Harmonic current emissions | --- | |||
Leakage current *3 |
100 V input | 0.5 mA max. | ||
200 V input | 1 mA max. | |||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 20 A max. | ||
200 V input | 40 A max. | |||
Output *4 |
Voltage adjustment range *5 | - 10% to 15% (with V. ADJ) (48-V models: ± 10%) | ||
Ripple *3 | 2% (p-p) max. | |||
Input variation influence | 0.4% max. with AC input voltage | |||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | |||
Temperature variation influence | 0.05%/ °C max. (at rated input and output) | |||
Startup time | 500 ms max. (up to 90% of output voltage at rated input and output) | |||
Hold time *3 | 20 ms min. | |||
Addi- tional func- tions |
Overload protection *6 |
105% to 175% of rated load current, voltage drop, intermittent, automatic reset |
||
Overvoltage protection *7 | Yes | |||
Overheat protection | No | |||
Parallel operation | No (However, backup operation is possible; external diodes required.) | |||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||
Protective circuit operation indicator |
No | |||
Other | Ambient operating temperature |
Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
||
Storage temperature | - 25 to 65 °C (with no icing or condensation) | |||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength |
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) |
|||
Insulation resistance |
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
|||
Vibration resistance |
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
|||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||
Output indicator | Yes (Color: Green) | |||
EMI |
Conducted Emissions |
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9 | ||
Radiated Emissions | Conforms to EN 55011 Group 1 Class A *9 | |||
EMS |
Electrostatic Discharge |
Conforms to EN61000-4-2 | ||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | |||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | |||
Surge | Conforms to EN61000-4-5 | |||
Conducted Disturbance |
Conforms to EN61000-4-6 | |||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | |||
Approved standards *9 | UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) | |||
cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 |
||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
||||
SEMI | SEMI F47-0200 (200-VAC input) | |||
Weight *8 | 300 g max. | 550 g max. |
Input specification | 100/200 V switchable | 100 to 240 V input | |||
---|---|---|---|---|---|
Power ratings *1 | 150 W at 5 V | 150 W at 12 V |
150 W at 24 or 48 V |
||
Efficiency | 5 V Models | 78% min. | --- | --- | |
12 V Models | --- | 79% min. | --- | ||
24 V Models | --- | --- | 86% min. | ||
48 V Models | --- | --- | 85% min. | ||
Input | Voltage *2 |
Switchable between 100 to 120 VAC (allowable range: 85 to 132 VAC) and 200 to 240 VAC (allowable range: 170 to 264 VAC). |
100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9) |
||
Frequency *2 | 50/60 Hz (47 to 450 Hz) | ||||
Current *3 |
100 V input | 3.5 A max. | 3.6 A max. | 3.5 A max. | |
200 V input | 2.1 A max. | 2.2 A max. | 2.1 A max. | ||
Harmonic current emissions | --- | ||||
Leakage current *3 |
100 V input | 0.5 mA max. | |||
200 V input | 1 mA max. | ||||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 20 A max. | |||
200 V input | 40 A max. | ||||
Output *4 |
Voltage adjustment range *5 | - 10% to 15% (with V. ADJ) (48-V models: ± 10%) | |||
Ripple *3 | 2% (p-p) max. | ||||
Input variation influence | 0.4% max. (with AC input voltage) | ||||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | ||||
Temperature variation influence | 0.05%/ °C max. (at rated input and output) | ||||
Startup time | 500 ms max. (up to 90% of output voltage at rated input and output) | ||||
Hold time *3 | 20 ms min. | ||||
Addi- tional func- tions |
Overload protection *6 |
105% to 175% of rated load current, voltage drop, automatic reset |
105% to 175% of rated load current, voltage drop, intermittent, automatic reset |
||
Overvoltage protection *7 | Yes | ||||
Overheat protection | No | ||||
Parallel operation | No (However, backup operation is possible; external diodes required.) | ||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | ||||
Protective circuit operation indicator |
No | ||||
Other | Ambient operating temperature |
Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
|||
Storage temperature | - 25 to 65 °C (with no icing or condensation) | ||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | ||||
Dielectric strength |
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) |
||||
Insulation resistance |
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
||||
Vibration resistance |
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
||||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | ||||
Output indicator | Yes (Color: Green) | ||||
EMI |
Conducted Emissions |
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9 | |||
Radiated Emissions | Conforms to EN 55011 Group 1 Class A *9 | ||||
EMS |
Electrostatic Discharge |
Conforms to EN61000-4-2 | |||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | ||||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | ||||
Surge | Conforms to EN61000-4-5 | ||||
Conducted Disturbance |
Conforms to EN61000-4-6 | ||||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | ||||
Approved standards *9 | UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) | ||||
cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 |
|||||
EN/VDE: EN50178 (= VDE 0160), Over voltage category III, EN 60950-1 (= VDE 0805Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
|||||
SEMI | --- | SEMI F47-0200 (200-VAC input) | |||
Weight *8 | 800 g max. | 700 g max. | 600 g max. |
Input specification | 100/200 V (Selected) | |||
---|---|---|---|---|
Power ratings *1 | 300 W | 600 W | ||
Efficiency | 5 V models | 71% min. | 72% min. | |
12 V models | 75% min. | 78% min. | ||
24 V models | 82% min. | 80% min. | ||
48 V models | 82% min. | 80% min. | ||
Input | Voltage *2 |
100 to 120 VAC (allowable range: 85 to 132 VAC) 200 to 240 VAC (allowable range: 170 to 264 VAC) (Switchable) |
||
Frequency *2 | 50/60 Hz (47 to 450 Hz) | |||
Current *3 |
100 V input | 8 A max. |
16 A max. (5V, 12V, 48V) 14 A max. (24V) |
|
200 V input | 4.5 A max. |
9 A max. (5V, 12V, 48V) 8 A max. (24V) |
||
Harmonic current emissions | --- | |||
Leakage current *3 |
100 V input | 0.5 mA max. | ||
200 V input | 1 mA max. | |||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 25 A max. | 30 A max. | |
200 V input | 50 A max. | 60 A max. | ||
Output *4 |
Voltage adjustment range *5 | -10% to 15% (with V. ADJ) (48-V models: ±10%) | ||
Ripple *3 |
2.8% (p-p) max.(5V) *6 2% (p-p) max.(12V, 24V, 48V) |
3.8% (p-p) max.(5V) *6 2% (p-p) max.(12V) *6 2% (p-p) max.(24V, 48V) |
||
Input variation influence | 0.4% max. | |||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | |||
Temperature variation influence | 0.05%/ °C max. | |||
Startup time | 650 ms max. | 500 ms max. | ||
Hold time *3 | 20 ms min. | |||
Addi- tional func- tions |
Overload protection *7 |
105% to 175% of rated load current, Inverted L voltage drop, the circuit will be shut OFF when the overload exceeds 5 s. (5V, 12V) *10 voltage drop, intermittent, automatic reset. (24V, 48V) |
105% to 175% of rated load current, Inverted L voltage drop, the circuit will be shut OFF when the overload exceeds 5 s. *10 |
|
Overvoltage protection *8 |
Yes (5V, 12V) *10 Yes (24V, 48V) *10 |
Yes *10 | ||
Overheat protection |
Yes (5V, 12V) *10 N0 (24V, 48V) *10 |
Yes *10 | ||
Parallel operation | Yes (up to 5 units) | |||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||
Protective circuit operation indicator |
Yes (color: red) (5V, 12V) No (24V, 48V) |
Yes (color: red) | ||
Other | Ambient operating temperature |
Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
||
Storage temperature | - 25 to 65 °C (with no icing or condensation) | |||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength |
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 25 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 25 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 25 mA) |
|||
Insulation resistance |
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
|||
Vibration resistance |
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
|||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||
Output indicator | Yes (Color: Green) | |||
EMI |
Conducted Emissions *3 |
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *11 | ||
Radiated Emissions | Conforms to EN 55011 Group 1 Class A *11 *12 | |||
EMS |
Electrostatic Discharge |
Conforms to EN61000-4-2 | ||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | |||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | |||
Surge | Conforms to EN61000-4-5 | |||
Conducted Disturbance |
Conforms to EN61000-4-6 | |||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | |||
Approved standards *13 | UL UR: UL 508 (Recognition), UL 60950-1 (Recognition) | |||
cUR: CSA C22.2 No. 60950-1 | ||||
EN/VDE: EN50178 (= VDE 0160), Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
||||
Weight *9 |
1,800 g max. (5V, 12V) 1,600 g max. (24V, 48V) |
2,500 g max. |
Input specification | 100 to 240 V input | ||||
---|---|---|---|---|---|
Power ratings *1 | 50 W | 100 W | 150 W | ||
Efficiency | 5 V Models | 73% min. | 78% min. | 79% min. | |
12 V Models | 76% min. | 78% min. | 78% min. | ||
24 V Models | 77% min. | 81% min. | 81% min. | ||
48 V Models | 80% min. | 81% min. | 82% min. | ||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9) | |||
Frequency *2 | 50/60 Hz (47 to 63 Hz) | ||||
Current *3 |
100 V input | 0.75 A max. | 1.4 A max. | 2.1 A max. | |
200 V input | 0.4 A max. | 0.75 A max. | 1.1 A max. | ||
Power factor | 0.9 min. | ||||
Harmonic current emissions | Conforms to EN61000-3-2 | ||||
Leakage current *3 |
100 V input | 0.5 mA max. | |||
200 V input | 1 mA max. | ||||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 17.5 A max. | |||
200 V input | 35 A max. | ||||
Output *4 |
Voltage adjustment range *5 | - 10% to 15% (with V. ADJ) (48-V models: ± 10%) | |||
Ripple *3 |
2% (p-p) max. This shall be 3% (p-p) or less when the ambient temperature is less than 0 °C (for only 5 V type). |
||||
Input variation influence | 0.4% max. with AC input voltage | ||||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | ||||
Temperature variation influence | 0.05%/ °C max. (at rated input and output) | ||||
Startup time | 1,000 ms max. | ||||
Hold time *3 | 20 ms min. | ||||
Addi- tional func- tions |
Overload protection *6 |
105% to 160% of rated load current, voltage drop, intermittent, automatic reset |
105% to 160% of rated load current, voltage drop, automatic reset |
||
Overvoltage protection *7 | Yes | ||||
Overheat protection | No | ||||
Parallel operation | No (However, backup operation is possible; external diodes required.) | ||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | ||||
Alarm indicator | No | ||||
Other | Ambient operating temperature |
Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
|||
Storage temperature | - 25 to 75 °C (with no icing or condensation) | ||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | ||||
Dielectric strength |
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) |
||||
Insulation resistance |
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
||||
Vibration resistance |
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
||||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | ||||
Output indicator | Yes (Color: Green) | ||||
EMI |
Conducted Emissions |
Conforms to EN 55011 Group 1 Class B and based on FCC Class B *9 | |||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *9 | ||||
EMS |
Electrostatic Discharge |
Conforms to EN61000-4-2 | |||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | ||||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | ||||
Surge | Conforms to EN61000-4-5 | ||||
Conducted Disturbance |
Conforms to EN61000-4-6 | ||||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | ||||
Approved standards *9 | UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) | ||||
cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 |
|||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
|||||
SEMI | SEMI F47-0706 (200-VAC input) | ||||
Weight *8 | 370 g max. | 550 g max. | 590 g max. |
Input specification | 100 to 240 V input | |||
---|---|---|---|---|
Power ratings *1 | 300 W | 600 W | ||
Efficiency | 5 V Models | 75% min. | 76% min. | |
12 V Models | 77% min. | 76% min. | ||
24 V Models | 79% min. | 78% min. | ||
48 V Models | 78% min. | 79% min. | ||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *8) | ||
Frequency *2 | 50/60 Hz (47 to 63 Hz) | |||
Current *3 |
100 V input | 4.5 A max. | 8.7 A max. | |
200 V input | 2.2 A max. | 4.3 A max. | ||
Power factor | 0.9 min. | |||
Harmonic current emissions | Conforms to EN61000-3-2 | |||
Leakage current *3 |
100 V input | 0.5 mA max. | ||
200 V input | 1 mA max. | |||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 17.5 A max. | ||
200 V input | 35 A max. | |||
Output *4 |
Voltage adjustment range *5 | -10% to 15% (with V. ADJ) (5 V, 48 V models: ±10%) | ||
Ripple *3 |
2% (p-p) max. 3% (p-p) max. (for only 5 V type) *12 |
|||
Input variation influence | 0.4% max. | |||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | |||
Temperature variation influence | 0.05%/ °C max. | |||
Startup time | 1,000 ms max. | |||
Hold time *3 | 20 ms min. | |||
Addi- tional func- tions |
Overload protection *6 |
105% to 160% of rated load current, voltage drop, intermittent, automatic reset. |
||
Overvoltage protection *7 | Yes | |||
Overheat protection | Yes | |||
Parallel operation | Yes (up to 5 Power Supplies) | |||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||
Remote sensing | Supported | |||
Remote control | Supported | |||
Alarm detection indication | Yes (color: red) | |||
Alarm output | Provided, open-collector output, 30 VDC max, 50 mA max. | |||
Other | Ambient operating temperature |
Refer to the derating curve in Engineering Data on Catalog. (with no icing or condensation). |
||
Storage temperature | - 25 to 75 °C (with no icing or condensation) | |||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength |
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 100 mA) 100 VAC for 1 min. (between all outputs and RC terminals; detection current: 100 mA) 500 VAC for 1 min. (between all outputs and ALM terminals; detection current: 20 mA) |
|||
Insulation resistance |
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
|||
Vibration resistance |
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
|||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions *10 | |||
Output indicator | Yes (Color: Green) | |||
EMI |
Conducted Emissions *3 |
Conforms to EN 55011 Group 1 Class B and based on FCC Class B *11 | ||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *11 | |||
EMS |
Electrostatic Discharge |
Conforms to EN61000-4-2 | ||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | |||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | |||
Surge | Conforms to EN61000-4-5 | |||
Conducted Disturbance |
Conforms to EN61000-4-6 | |||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | |||
Approved standards *8 |
UL UR: UL 508 (Recognition) *13 UL Listed: UL508 (Listing) *14 UL UR: UL 60950-1 (Recognition) |
|||
cUR: CSA C22.2 No.107.1, CSA C22.2 No. 60950-1 | ||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
||||
SEMI | SEMI F47-0706 (200-VAC input) | |||
Weight | 1,200 g max. *9 | 1,800 g max. *9 |
Temporarily attach the enclosed mounting bracket as shown in the illustration on the right, hook the holes (parts a) in the Power Supply on hooks on the mounting bracket (parts b), and secure the Power Supply with two mounting screws.
Note: Mounting screws are not provided.
Note: Mounting Brackets are provided in a set, one for the right side and one for the left side.
(Please ask your dealer for details of delivery.)
For 30-W/50-W/100-W/150-W/300-W/600-W models (separately purchasable)
The mounting-hole pitch of mounting brackets A - I below is identical to that of our product S82J. These brackets can be used for switchover with the S82J-series.
Note:Mounting brackets (A, B, C, D, E, F, G, H, I) are compatible with S82J mounting holes.
Screws used
A: Accessories (4 locations)
Be sure to use the accessory screws.
Note: For ventilation of the back surface, the body should be placed 23.6 mm in front of the mounting side.
Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail.
Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail.
* Value in parentheses are for PFP-50N.
Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail.
Note: Use a metal DIN Rail when mounting a 600-W model to a DIN Rail.
50-/100-/150-W Models
Temporarily attach the enclosed mounting bracket as shown in the illustration on the right, hook the holes (parts a) in the Power Supply on hooks on the mounting bracket (parts b), and secure the Power Supply with two mounting screws.
Note: Mounting screws are not provided.
* Value in parentheses are for PFP-50N.
TITLE | DOCUMENT TYPE | SIZE |
S8JX | Catalog | 12429 KB |
---|---|---|
S8JX Switching Power Supply (ENG/JPN/ITA/GER/FRE/SPA) |
Manual | 602 KB |
S8JX (300 W, 600 W) Switching Power Supply |
Manual | 720 KB |
S8JX-P (50 W, 100 W, 150 W) Switching Power Supply |
Manual | 2538 KB |
S8JX-P (300W, 600W) Switching Power Supply (1/2) (ENG/JPN/ITA/GER/FRE/SPA) |
Manual | 1993 KB |
S8JX-P (300W, 600W) Switching Power Supply (2/2) |
Manual | 286 KB |
S82Y-JXP[](L)FAN Fun Unit (ENG/JPN/ITA/GER/FRE/SPA) |
Manual | 398 KB |